Technical data KWD

Nominal data

Terminal

KWD 1

KWD 1-F

KWD 2

KWD 2-F

KWD 4-F

KWD 5

Input voltage (UZP, UZN)

(Power supply)

 

X05

540 VDC

(max. 720 VDC)

Input current at 540 VDC

(Power supply)

 

X05

 

3.8 A

 

7.6 A

 

15.2 A

 

19 A

Shutdown threshold of the DC bus voltage

 

850 VDC

Supply voltage

(Logic supply)

 

X08

X09

 

24 VDC

Input power

(Logic supply)

 

24 W

Efficiency

 

approx. 98%

 

Control procedure/switch frequency

 

PWM / 8 kHz

Output frequency 1)

KW-R03(P) / KW-R04

KW-R05 / -R06 / -R16 / -R24(-R) / -R25 / -R26

 

X04

 

0 - 800 Hz

0 - 1200 Hz

Output voltage

X04 A/B

0 - 350 VAC (sine-shaped output current)

Output rated power at 3 x 350 VAC

X04 A/B

2 x 1 kVA

2 x 2 kVA

2 x 4 kVA

2 x 5 kVA

Output rated current IN

X04 A/B

2 x 1.65 A

2 x 3.3 A

2 x 6.6 A

2 x 8.25 A

Peak output current Imax2)

X04 A/B

2 x 3.3 A

2 x 6.6 A

2 x 13.2 A

2 x 16.5 A

Max. time

Peak output current Imax

X04 A/B


Output frequency fout > 1 Hz

10 s

Output frequency fout ≤ 1 Hz

0.5 s

 

Protective/ 
monitoring functions

 

Motor over-current / short-circuit / short-to-ground,
Excess temperature - heat sink / motor - current overload after I²t

Cooling

 

KW x = External air or liquid cold plate

KW x-F = Integrated air cooling

Max. cold plate or ambient temperature

 

 

40 °C

Module width

 

55 mm

Weight

 

3 kg

1)

Valid for devices with firmware versions beginning up from V2.12 2018/03:

V/f-operation:

Output frequency max. 599 Hz

Closed control loop operation:

Speed setpoint values are limited to 30000 rpm. The actual speed value is monitored for the maximum speed of 30000 rpm. Actual speed values are detected above 30000 rpm. The drive generates the error 2319 'n > nmax 'and runs down.

2)

The max. duration of power output current Imax is lowered in DC operation (moving on block/stop). The limit speed between normal and DC operation can be defined using the following formula.

Additional information: Note on application No. AP 2008_05-1d

 

 

The maximum duration of peak output current lmax is based on twice the output power of the inverter. The maximum duratin of power current output tmax can be calculated for any output current. The I2t constant is c = 30 at tmax = 10 s and c = 1.5 at tmax = 0.5 s.

 

 

Formula: Any I2t constant c

 

Additionally, the evaluation of the temperature of the rear panel of the module and the temperature model (KW-R06) provide the best possible protection for the module in DC operation (moving on block) and during cyclic overload with simultaneous high basic load.