ACC bus interface

The ACC bus interface is a CAN bus interface with an additional hardware synchronisation line used to synchronise the inverter modules with the transfer protocol DS301, version 4.01. The compact power supply can send and receive data via the ACC bus interface. The send and receive data is mapped in PDOs. The transfer type is 254: asynchronous PDO, event-guided. The minimum cycle time for cyclical PDO transmission is 10 ms.

The entire CANopen functionality is defined in the device description file KER3_207_0604.eds. EDS files can be downloaded on the AMK website.

The compact power supply is an ACC bus slave participant with the default address 33 (21 hex). Other KE addresses (address "34" ... "39" are permitted) must be preset in encoded form via the DIP switch S1 in the KE front panel. The baud rate is preset at the factory to 1000 kBd (default value). Further information: Siehe 'Changing the default settings'..

 

ACC bus-specific characteristics 

The SBM output indicates the fault-free status of the module after initialisation.

In case of an error in the SBM the System Ready is reset and the main contactor is released.

 

ACC bus interface status

Other ACC bus subscribers

KE response

KE ACC bus interface enabled

An ACC bus master + x other slaves available

SBM is set

KE ACC bus interface enabled

No ACC bus subscribers

SBM is set after 15 seconds

KE ACC bus interface disabled

(all S1 DIP switches ON)

 

SBM is set

KE ACC bus interface enabled

Configuration ID32795 Source UE

= signal via ACC bus (e.g. code 5)

No ACC bus subscribers

Set after 15 seconds

PDO mapping variables

All three transmit variables (iMessage16, diMessage32 and wDeviceState) must be mapped for the compact power supply. It is not permitted to only configure one of the three variables. The PDO is transferred event-guided (transfer type EVENT). The shortest possible cycle time for this message is 10 ms.

Configurable feedback values 

API variable name

CAN index

CAN sub-index

Copy
direction

Use

iMessage16

0x2040

0x01

Tx

Configurable, cyclical 16-bit feedback value message
(ID32785 'Message 16')

diMessage32

0x2040

0x02

Tx

Configurable, cyclical 32-bit feedback value message
(ID32786 'Message 32')

Status and control variables

API variable name

CAN index
[hex]

CAN

sub-index [hex]

Copying

direction

Use

wDeviceState

0x2048

0x00

Tx

Status bits

Bit

Syntax

Meaning

0

SBM

System ready message

1

DC Bus Enable

Acknowledgement 'Converter ON'

2

QFL

Acknowledgement clear error

3

-

-

4

WARN

Warning message

5

ERR

Error message

6..15

-

-

wDeviceControl

0x2049

0x00

Rx

Control bits

Bit

Syntax

Meaning

0

FL

Clear error

1

DC bus enable

Converter ON

2..15

-

-