KW-CPxx cold plates
The cold plate is fitted on the mounting plate in the switch cabinet.
Fastening: 4 screws M8 (KW-CP340 / 420 / 510 / 680(R)) or 8 screws M8 (KW-CP1000 / -CP1035R).
The assembly must be carried out on a flat surface (flatness ≤ 0.3 mm). The cold plate must not be braced during the assembly.
If several cold plates are assembled on top of each other, an upward and downward minimum distance of 100 mm each must be observed. The distances between signal and power cables must be complied with. Furthermore, please take note of the fact that the electronic components are cooled by internal fans, and that the air inlet temperature must not exceed 40 °C even in the top row.