Description:
Auxiliary contacts
For the contactor type 25A (204297), the auxiliary contacts are integrated in the contactor.
The contactor types 80 A (29297), 90 A (29298) and 230 A (200446) contain external auxiliary contacts.
The contactor 45A (204298) needs additional external auxiliary contacts (204300).
Technical data:
- Auxiliary voltage: 24 - 690 VAC, 24 - 250 VDC
Version:
Type |
Pins |
---|---|
Screw terminal |
1 |
Assignment:
Designation |
Connection |
---|---|
11 / 12 21 / 22 31 / 32 |
Terminals of NC contacts |
13 / 14 43 / 44 |
Terminals of NO contacts |
Connection:
Module |
25A |
45A |
80A |
90A |
---|---|---|---|---|
AMK part no. |
204297 |
204297 |
29297 |
29298 |
Recommended cable type |
2-wire, unshielded |
|||
Cable assembly |
Wire end ferrule with plastic sheath |
|||
Wire cross-section |
1 mm2 AWG 16 |
1 mm2 AWG 16 |
2.5 mm2 AWG 12 |
2.5 mm2 AWG 12 |
Tightening torque |
1.2 Nm |
1.2 Nm |
1.0 - 1.2 Nm |
1.0 - 1.2 Nm |
Module |
230A |
---|---|
AMK part no. |
200446 |
Recommended cable type |
2-wire, unshielded |
Cable assembly |
Wire end ferrule with plastic sheath |
Wire cross-section |
2.5 mm2 AWG 12 |
Tightening torque |
1.0 - 1.2 Nm |