Mains filter AF 15-SI, AF 45-SI, AF 60-SI, AF 90-S, AF 180-S and AF 270-S

Designation

AF 15-SI

AF 45-SI

AF 60-SI

AF 90-S

Nominal voltage

3 x 480 V
50 / 60 Hz

Nominal current

3 x 15 A

3 x 45 A

3 x 60 A

3 x 90 A

Supply voltage

(Logic supply)

-

24 VDC

0,25 A

Overload factor

4 x IN for 10 s

4 x IN for 10 s

5 x IN for 10 s

2 x IN for 10 s

Leakage current

< 100 mA1)

Power loss

53 W

140 W

155 W

210 W

Protection class

IP 20

Weight

7.5 kg

11.5 kg

14.5 kg

15 kg

Dimensions
W x D x H / mm

83 x 205 x 320

165 x 218 x 347

165 x 218 x 347

174.5 x 260 x 340

AMK part no.

O915

O927

O940

O825

1)

According to norm IEC 950 for symmetrical TT or TN networks

For network switch on and switch off or line unbalance leakage currents greater than 800 mA can occur.
Specification reg. 50/60 Hz (for f = 8 kHz: I < 1 A)

 

Designation

AF 180-S

AF 270-S

Nominal voltage

3 x 480 V
50 / 60 Hz

Nominal current

3 x 180 A

3 x 270 A

Supply voltage

(Logic supply)

24 VDC

0.5 A

24 VDC

0.7 A

Overload factor

1.67 x IN for 10 s

1.78 x IN for 10 s

Leakage current

< 100 mA1)

Power loss

370 W

500 W

Protection class

IP 20

Weight

19 kg

73 kg

Dimensions
W x D x H / mm

174.5 x 310 x 400

Wall mounting

349 x 300 x 454

 

Floor mounting2)

380 x 305 x 460

AMK part no.

O812

O946

1)

According to norm IEC 950 for symmetrical TT or TN networks

For network switch on and switch off or line unbalance leakage currents greater than 800 mA can occur.
Specification reg. 50/60 Hz (for f = 8 kHz: I < 1 A)

2)

Foot angle required (option 47869)