Codes for the configuration of the binary inputs
|
Code |
Designation |
Description |
|---|---|---|
|
0 |
Function inactive |
No function assigned to the binary input |
|
400 |
Homing switch (cam) |
For cam see 32905 |
|
401 |
Touch probe (MT1) |
Measurement signal 1 for touch probe function only at BE3 ( |
|
402 |
Touch probe (MT2) |
Measurement signal 2 for touch probe function only at BE2 ( |
|
32903 |
DC bus ON (UE) |
Charge DC bus |
|
32904 |
Controller enable (RF) |
Activate control |
|
32905 |
Homing switch (cam) |
Cam signal, e.g. for the homing cycle |
|
32912 |
Reset "homing point known" |
Clear "homing point known" |
|
32913 |
Clear error (FL) |
Existing errors in the drive are reset |
|
33700 |
Activate main operating mode |
Change operating mode to the main operating mode ( |
|
33701 |
Activate secondary operating mode 1 |
Change operating mode to the auxiliary operating mode 1 ( |
|
33702 |
Activate secondary operating mode 2 |
Change operating mode to the auxiliary operating mode 2 ( |
|
33703 |
Activate secondary operating mode 3 |
Change operating mode to the auxiliary operating mode 3 ( |
|
33704 |
Activate secondary operating mode 4 |
Change operating mode to the auxiliary operating mode 4 ( |
|
33705 |
Activate secondary operating mode 5 |
Change operating mode to the auxiliary operating mode 5 ( |
|
33708 |
Stop / cancel CMD |
The drive changes to the operating mode of digital speed control with the setpoint 0 regardless of the current operating mode |
| 33709 |
Dig. Speed control N = 0 U/min |
CMD digital speed control Speed setpoint N-setpoint= 0, ramp active |
| 33710 |
Dig. Speed control N = |
CMD digital speed control Speed setpoint N-setpoint |
| 33711 | Homing cycle | CMD homing cycle for homing point (Xi=0) |
| 33721 |
Dig. Torque control M = 0 %Nm |
CMD digital torque control Torque setpoint M-setpoint = 0 |
| 33722 |
Dig. Torque control M = |
CMD digital torque control Torque setpoint M-setpoint = |
|
33730 |
System booting |
Complete parameter calculation for inactive controller enable. The recalculation otherwise takes place only after the mains is on, error cleared and RF is activated after changing the parameter. |
|
33735 |
Control of the motor holding brake |
Manual control of the motor holding brake via digital input 0 → 1 edge: Open motor holding brake 1 → 0 edge: Close motor holding brake
This 'Controlling motor holding brake' |
|
33906 |
Acknowledgement signal of the motor holding brake (QBR) |
Acknowledgement motor holding brake (QBR) QBR = 1: Motor holding brake closed QBR = 0: motor holding brake opened (QBR is supplied by the motor holding brake)
This 'Controlling motor holding brake' |
|
33909 |
Stop positive setpoint processing |
If the configured binary input falls to zero volts (low active), the setpoint block takes place in the position or speed control within 2 ms. If the input is set, the setpoint enable takes place within 2 ms. |
|
33910 |
Stop negative setpoint processing |
If the configured binary input falls to zero volts (low active), the setpoint block takes place in the position or speed control within 2 ms. If the input is set, the setpoint enable takes place within 2 ms. |
|
33940 |
Hardware limit switch positive direction |
The drive is braking according The hardware limit switch function is not active if the function homing cycle with hardware limit switch evaluation (ID147 bit 9) is active! |
|
33941 |
Hardware limit switch negative direction |