ID11 'Status class 1-errors'

Sphere of action:

FORMAL

Default value:

0000 0000 0000 0000

Access:

READING

Scale:

-

Temporarily changeable:

NO

Unit:

-

Data length:

2 byte

Min. value:

-

Signed:

NO

Max. value:

-

Format:

BIN

 

 

List:

NO

 

 

If an error of the 'Status class 1-errors' is detected in the drive, an error-bit is set in ID11 'Status class 1-errors' and bit 13 in ID135 'Drive status word'. 'Status class 1-errors' and bit 13 in ID135 'Drive status word' can only be reset if there is no longer any error and the command ID99 'Diagnosis reset status class 1' was successfully executed.

Before the controller enable RF is withdrawn internally, the drive attempts to brake the motor to a stop in a regulated manner. If braking cannot take place, the controller enable RF is withdrawn and the motor runs out to stop.

 

Construction ID11 'Status class 1-errors'

Bit no.

Condition

Meaning

0

0

No error

1

Error present:

  • Motor overload shutdown
  • The I2t-monitor motor must be activated in ID32773 'Service bits' Bit 14.

  • Configuration of the temperature model is faulty (have SEEP data checked by AMK Service).
  • IGBT temperature greater than the limit temperature specified for the device (have SEEP data checked by AMK Service).

1

0

No error

1

Error present:

Overtemperature of the converter, shutdown

The parameter 'Temperature internal' is longer than the 'Warning time' above the specified threshold value for the device (SEEP device).

2

0

No error

1

Error present:

Overtemperature of the motor, shutdown

'Temperature external' is above the threshold value according to ID34166 'Warning time' longer than ID32943 allows 'Temperature sensor motor'.

If the value in ID34166 = 0, then the limit value is 140°C.

3

0

Reserved

1

Reserved

4

0

No error

1

Error present:

Supply voltage 24 VDC error

5

0

No error

1

Error present:

Error in the encoder signal feedback, e.g. break in the encoder cable or encoder error.

6

0

Reserved

1

Reserved

7

0

No error

1

Error present:

Converter overcurrent

An unacceptably high converter current was detected, e.g. due to short-circuit or earth contact.

8

0

No error

1

Error present:

DC bus overvoltage

The DC voltage in the DC bus has exceeded the permissible threshold value.

9-10

0

Reserved

1

Reserved 

11

0

No error

1

Error present:

Excessive control deviation

The difference between the position setpoint and actual position value (ID189 'Following distance') is greater than ID159 'Excess error'.

12

0

No error

1

Error present:

Communications error

13

0

Reserved

1

Reserved

The message that the position threshold value is exceeded according to ID49 and ID50 is only available in ID182 'Diagnosis manufacturer status' Bit 0.

14

0

Reserved

1

Reserved

15

0

No error

1

Manufacturer-specific error present:

Siehe ID129 'Manufacturer status class 1'.