Technical data

Cold plate

KW-LK110

KW-LK250

KW-LK400

KW-LK500

Part no.

O745

O743

O744

O802

Maximum removable power

120 W

600 W

900 W

1200 W

Ambient temperature

0 ... 40°C

0 ... 40°C

0 ... 40°C

0 ... 40°C

Fan voltage
(red +,blue -)1)

24 VDC ± 10%

24 VDC ± 10%

24 VDC ± 10%

24 VDC ± 10%

Fan flow

0.3 A

0.75 A

1.0 A

1.5 A

Cable length

300 mm

300 mm

300 mm

300 mm

Protection class

IP 20 2)

IP 20

IP 20

IP 20

Dimensions
(B x T x H)

108 x 46 x 418 mm

260 x 85 x 465 mm

410 x 85 x 465 mm

510 x 85 x 465 mm

Cooling surface (B x H)

105 x 320 mm

250 x 320 mm

400 x 320 mm

500 x 320 mm

Effective width in case of
through-hole mounting
--

220 mm

370 mm 470 mm

Weight

about 2 kg

about 10 kg

about 16 kg

about 19 kg

1)

24 VDC must be supplied externally

2)

Mounted on mounting plate in the switch cabinet (See 'Mounting KW-LK110'.)