Mains chokes ALN xx
Designation |
ALN 12 |
ALN 17 |
ALN 36 |
ALN 36 / 1000 |
ALN 63 |
---|---|---|---|---|---|
Nominal voltage UN |
3 x 500 V, 50 / 60 Hz* |
||||
Nominal current IN |
3 x 12 A |
3 x 17 A |
3 x 36 A |
3 x 36 A |
3 x 63 A |
Maximum current [rms] |
30 A for 20 s (2.5 x IN) |
54 A for 60 s (3.17 x IN) |
54 A for 60 s (1.5 x IN) |
100 A for 60 s (2.77 x IN) |
94 A for 60 s (1.5 x IN) |
Short circuit voltage uk |
4 % at 50 Hz |
3.9 % at 50 Hz |
4 % at 50 Hz |
4 % at 50 Hz |
4 % at 50 Hz |
Inductance/Line |
3 mH |
2.1 mH |
1 mH |
1 mH |
0.58 mH |
Power loss |
50 W |
60 W |
80 W |
80 W |
120 W |
Protection class |
IP 00 |
||||
Weight |
3.6 kg |
4 kg |
6 kg |
7 kg |
10 kg |
Dimensions |
Siehe 'Mains chokes ALN 12 ... ALN 150 / ALN 15-SI ... ALN 90-S'. |
||||
AMK part no. |
O911 |
O742 |
O726 |
O727 |
O728 |
Designation |
ALN 85 |
ALN 125 |
ALN 150-2,5 |
ALN 180 |
ALN 270 |
---|---|---|---|---|---|
Nominal voltage UN |
3 x 500 V, 50 / 60 Hz* |
||||
Nominal current IN |
3 x 85 A |
3 x 125 A |
3 x 150 A |
3 x 180 A |
3 x 270 A |
Maximum current [rms] |
127 A for 60 s (1.5 x IN) |
187 A for 60 s (1.5 x IN) |
300 A for 60 s (2 x IN) |
330 A for 60 s (1.83 x IN) |
480 A for 60 s (1.77 x IN) |
Short circuit voltage uk |
4 % at 50 Hz |
4 % at 50 Hz |
2.5 % at 50 Hz |
2 % at 50 Hz |
4 % at 50 Hz |
Inductance/Line |
0.43 mH |
0.295 mH |
0.15 mH |
0.125 mH |
0.137 mH |
Power loss |
180 W |
210 W |
300 W |
300 W |
425 W |
Protection class |
IP 00 |
||||
Weight |
16 kg |
20 kg |
27 kg |
27 kg |
62 kg |
Dimensions |
Siehe 'Mains chokes ALN 12 ... ALN 150 / ALN 15-SI ... ALN 90-S'. |
||||
AMK part no. |
O729 |
O730 |
O731 |
O739 |
O965 |
* IT network: Voltage range is restricted here to
3 x 400 V -20%... 440 V + 10 %, 47 ... 63 Hz