[X01] terminal L1 / L2 / L3 / PE mains connection - mains transmission

DANGER

Danger to life from touching electrical connections!

Electrical terminals and connectors carry voltages that may cause death or serious injury upon contact.

When the LEDs on the front panels are OFF, this does not indicate that the electrical terminals have been de-energized.

Steps to prevent:

  • Prior to any work on the device: Observe the 5 safety rules.
  • Measure the terminal voltages. There may be no voltage present.
  • Plug and pull connections only when there is no voltage.
  • For devices that are connected to a DC bus, or generate it yourself, you need to consider the discharge times of the dc bus capacitors mentioned in the converter documentation
  • Before commencing work, the connections must be isolated from the voltage supply at both ends! (both ends mean: AC and DC bus supply side )

Description

Siehe 'Layout of the iC mains connection'.

Technical data

Siehe 'Technical data iC'.

Design

Type

Pole

Sort

Manufacturer

Designation

Terminal with tension spring connection

9

 

WAGO

745

Actuating tool: Screwdriver with a blade 3.5 x 0.5 mm

The cable is attached to the housing: Cable gland M25 x 1.5

Assignment

[X01]

Connection

Signal

Description

Siehe 'Terminal box (iC)'.

1

L1

Mains phase L1

2

L1

Mains phase L1 transmission

3

L2

Mains phase L2

4

L2

Mains phase L2 transmission

5

L3

Mains phase L3

6

L3

Mains phase L3 transmission

7

PE

Protective earth

8

PE

Protective earth

9

PE

Protective earth

Connection

Cable

4 x 1.5 mm2 / AWG 16

4 x 2.5 mm2 / AWG 14

 

Max. conductor cross-section of the terminal

Flexible cable with a wire end sleeve with plastic collar 2.5 mm2

Stripping length

11 - 12 mm

Shield connection

-