[X08] Supply voltage 24 VDC and STO supply line

Note only for devices with rev.<4.00:

NOTE

Material damage!

Material damage due to overvoltage!

An overvoltage at the connections X08 and X09 (24 VDC) is not monitored and damages the device1). (

Steps to prevent:

  • Comply with the specifications for the electronics supply voltage 24 VDC.
    (24 VDC ± 15 %, ripple max. 5 %)

1)

Devices with Rev. <4.00 do not have STO certification (no TÜV logo on the nameplate) and do not have overvoltage monitoring. An overvoltage > 24 VDC ± 15% at 24V or STO will destroy the device.

Assignment

[X08] in terminal box

Connection

Signal

Description

1

24V 1)

Supply voltage 24 VDC for electronic and an optional motor holding brake.

2

0V

Reference potential for 24 VDC (Connection 1)

3

STO 1)

STO (Safe torque off)

The supply voltage directly controls the STO state.

Siehe 'STO (Safe torque off)'.

4

STO_GND

Reference potential for STO (Connection 3)

1) 

Maximum current of the terminal: 10 A

Maximum current hybrid cable : 6 A

The current of the 24 VDC supply voltage must be limited by the user!

 

Siehe 'Connection box ihX'.

 

Technical data

Description

  • 24 VDC supply voltage supply line
  • Connection of the control signal STO and STO_GND
  • Transmission to further drives or Hybrid Cable Interface Board via terminal [X09]

Connection design

Terminal (on the device)

connector, 4-poles, 1-row pin strip

Mating plug

4-poles, socket

Electrical data

Siehe 'Electrical data ihX'.

Cable

2 x 1,0 mm2 + 2 x 0,5 mm2, flexible

cable assembly

Wire end ferrule with plastic sheath

Accessories

Prefabricated cable:

Siehe 'Hybrid cable configured'.

Notes

PELV power supply (Protective Extra Low Voltage): functional extra-low voltage with safe separation

The voltage must also be limited to a maximum of 60 VDC in the event of an error. The 0 VDC potential of the power pack must be grounded at the central PE.